Call us now :

+8618042002123

Email us now :

xucg@reallin.com

D1006-BF Series Single Phase Meter for DIN Rail

Welcome to choose single phase Din Rail meter. Let’s introduction it’s functions and operations of this product.

Description

Din Rail Energy Meter

▌Common

This meter is 1phase – 2wire direct connected electricity meter. It adopts the advanced technology of LSI (Large Scale Integrated circuit) and digital signal processing. The craftworks of our product are exquisite and the functions provided are comprehensive and client-oriented. The energy meter is an intelligent instrument equipped with leading technology.

The functionality of the single phase Din Rail energy meter includes active energy measurement,instantaneous measurement for voltage, current, frequency, power factor and power, RS485

communication, self-check.

▌Appropriate Use

The electricity meter D1006-BF series are allowed to be used for measuring electrical energy only.

Type Designation

Type

Description

D1006-BFB Import & Export measurement, with S0 output and terminal cover detection
D1006-BFC Import & Export measurement, without S0 output and terminal cover detection
D1006-BF1 Import measurement only, with S0 output and terminal cover detection
D1006-BF2 Import measurement only, without S0 output and terminal cover detection
D1006-BF3 Import & Export measurement, with S0 output, without terminal cover detection

Properties

Type Single phase electricity meter direct connection
Voltage
Nominal voltage Un 230 VAC
Voltage range 0.8 – 1.2 Un
Frequency
Nominal frequency fn 50Hz
Frequency range 0.98 – 1.02 fn
Current
Reference current Iref = Ib = 10 Itr 5 A
Maximum current Imax 65A
Minimum current Imin 0.25 A
Starting current Ist 0.004 Ib
Accuracy
Active Class B in compliance with DIN EN 50470-3 Class 1.0 in compliance with IEC 62053-21
Reactive Class 2.0 in compliance with IEC 62053-23
Measuring Active Energy
Two energy directions +A/-A, +R/-R,
Reverse locking +A, +R,
Meter constant
LED-Output 1000 imp/kWh, 1000 imp/kvarh
Display
LCD 6 digit

 

Life cycle > 12 years
RS485- Data Interface
Connector Two screws type
Parameter 1200/2400/4800/9600/19200/38400/115200 bps,

8E1/8N1/8O1(parameters adjustable)

Communication protocol Modbus RTU
Power Consumption
Voltage circuit < 1.5 W / 8 VA at Un
Current circuit < 1 VA at Ib
Temperature Range
Typical Operation -30°C to +70°C
Storage -40°C to +85°C
Humidity 95% RH, Non considering
EMC Properties
Isolation 4 kV AC, 50 Hz, 1min
High Voltage 7kV, Impulse 0.1/2000 µs
Housing
Dimension DIN-Rail 90x35x62 mm
Material fiber-glass reinforced Polycarbonat (flame resistant EN 62053-21, recyclable)
Class of protection II
Degree of protection IP 20(IP 51 in protective enclosure), indoor
Weight
Weight appr. 0,13 kg

Tab. 2: Technical Properties

D1006-BF Series Single Phase Meter for DIN Rail

Additional information

Certification

MID, UL

Accuracy

Class 2.0 for reactive, Class B/1.0 for active

Reviews

There are no reviews yet.

Be the first to review “D1006-BF Series Single Phase Meter for DIN Rail”

Your email address will not be published. Required fields are marked *

Recent Products